Products

Hornbill 4000

Hornbill Static switch have different user selectable parameters with DSP control. It is excellent performance enhancement system for useful in Data centers, Process Automation, Power plants, Healthcare, Telecom, broadcasting, Industry type of environment.

  • Features & Benefits

  • Technical Specifications

  • Documentation

     

    • 32 bit DSP based design
    • Automatic instantaneous transfer and retransfer without cross connection of sources
    • Enhanced monitoring and diagnostics
    • RS 232 or RS 485 interface with MODBUS protocol
    • 128 x 64 Graphics display
    • Metering : Current, Voltage and Frequency
    • Redundant power supply
    • Redundant fans for cooling
    • Inrush current limiting (optional)
    • Complies with IEEE 446
MODEL Hornbill 4000
Input / Output  
Nominal Voltage 220 / 380 / 400 / 415 V AC (3 Ph + N)
Voltage Tolerances +/- 15%
Frequency Tolerances 50 - 60 Hz (Auto selectable)
Power Capacity 63 A 100 A 200 A 300 A
No. of Switching Poles FOUR
Overload Capacity 110 % for 1 hour, 150 % for 1 min., 200 % for 10 sec., 1000 % for 100 ms
Duty Continuous
Load Power Factor Range 0.2 to Unity leading or lagging
Source Voltage Distortion < 10 % THD
Switch  
Transfer < 5 ms
Retransfer < 5 ms
Manual Bypass Provided
Environmental  
Acoustic Noise @ 1m (Ref. ISO 3746) ≤ 55 dBA ≤ 58 dBA
Operating Temperature 0 to 40 °C
Storage Temperature 0 to 70 °C
Relative Humidity Up to 95 % (Non Condensing)
Altitude < 1000 meters above sea level (without de-rating) altitude
Physical  
Enclosure Protection IP - 20
Cooling Forced Air
Colour RAL 7016
Cable Entry Bottom
Dimensions (mm) W x D x H 800 x 500 x 1500 1000 x 700 x 1750
Installation Free standing, floor mounted
User Interface  
Indications Source 1 Healthy, Source 1 Priority, Source 1 Feeding, Source 1 Manual bypass ON, Output ON
Source 2 Healthy, Source 2 Priority, Source 2 Feeding, Source 2 Manual bypass ON, No Sync
Fault Indication Overload
Display 128 x 64 Graphics Display
Metering Source 1 & Source 2 - Voltage, Current, Frequency, Output Voltage, Output Current
Standards IEC 62310-1, IEEE 446
Communication  
Interface & Protocol RS 232
Available Options RS 485 MODBUS, Ethernet connectivity

Specifications are subject to change without prior notice due to constant improvement in design & technology.
Custom models available on request.

ENQUIRY

CUSTOMER SUPPORT
078 1000 9955

ASK PROF. WATT

Looking for help to identify a solution for your home or business?

Ask Prof. Watt >

ASK PROF. WATT

NEWS

Manufacturing units without electricity grid connections a reality
Apr 29, 2017 | The Machinist

Textile Industry investing in efficient power management systems
Apr 3, 2017 | The Textile Magazine

Consul Neowatt view of Power Sector
Jan 24, 2017 | Power Watch Magazine

3 Phase large UPS systems give Consul Neowatt the edge
Dec 28, 2016 | DT Next

Read more >
 

MOBILE APP

MOBILE APP

The Consul Neowatt Warranty and Service app puts the warranty / service information of your Consul Neowatt product in the palm of your hand.

CLICK HERE

Client Speak